CVE-2024-31854 HIGH

CVE-2024-31854

Vendor Siemens
Product SICAM TOOLBOX II
Weakness CWE-295
Published July 8, 2025
Last update July 8, 2025

CVSS base score

8.1/10
Attack vector Network
Attack complexity High
Privileges required None
User interaction None
Confidentiality High
Integrity High

CVSS vector

CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

What the vulnerability does

01Description

A vulnerability has been identified in SICAM TOOLBOX II (All versions < V07.11). During establishment of a https connection to the TLS server of a managed device, the affected application doesn't check device's certificate common name against an expected value. This could allow an attacker to execute an on-path network (MitM) attack.

Key dates

02Disclosure timeline

July 8, 2025 CVE published